Fire Alarm Control Panel FA-605/610 |
Specification |
|
|
|
|
|
Model |
|
FA-605 (5 Zone), FA-610 (10 Zone) |
Power |
|
110/220VAC 50/60Hz |
|
Voltage Scope |
|
Nominal voltage ± 20% |
|
Standby Power |
|
24VDC 0.8Ah ~ 2.1Ah (battery backup) |
Charging Voltage, Current |
|
26VDC 100mA ~ 400mA |
|
Loop Voltage, Current |
|
24VDC short circuit under 5V 30mA |
Exterior Resistance |
|
Round-trip under 50W |
|
# of heat detector connected |
|
No limit |
|
|
|
# of smoke detector connected |
|
30/loop |
|
|
|
# of indicating lamp, bell connected |
|
# of loop x 1.2 |
|
|
Digital Switch |
|
500000 Cycles Min. reliability |
|
End of Line Resistor |
|
10 kW (one per loop) |
|
Material |
|
1.2 mm steel plate |
|
|
Color |
|
lvory white |
|
|
Dimensions |
|
350 mm (H) x 285 mm (W) x 105 mm (D) |
Accessory Functions |
|
Dual signal transfer contacts, aux.contacts |
Fire Alarm Detector |
|
|
Rate of Rise Heat Detector S-302 |
|
|
|
|
|
Effective Alert Area |
|
|
|
|
|
construction/Height |
|
Under 4M |
|
4M ~ 8M |
|
Fire-proof Building |
|
90 M2 |
|
45 M2 |
|
Ordinary Building |
|
50 M2 |
|
30 M2 |
Specification |
Type |
|
2-wire |
|
3-wire |
|
4-wire |
Alarm Contact |
|
N/A |
|
N/A |
|
0.8A @ 30VDC |
|
|
|
|
|
|
0.4A @ 125VAC |
Alarm Temperature |
|
Comply to EN54, CNS |
|
|
|
|
Voltage Range |
|
12 ~ 30VDC |
|
|
|
|
|
|
Alarm Current |
|
25 mA |
|
|
|
|
|
|
Ambient Temperature |
|
0°C ~ +55°C |
|
|
|
|
Material |
|
Fire-proof plastic |
|
|
|
|
Dimensions |
|
102 mm (Dia) x 45 mm (H) |
|
|
Weight |
|
About 130g |
|
|
|
|
|
|
Color |
|
White |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Fixed Temperature Detector S-318 |
|
Effective Alert Area |
|
|
|
|
construction/Height |
|
Under 4M |
|
4M ~ 8M |
Fire-proof Building |
|
60 M2 |
|
55 M2 |
Ordinary Building |
|
30 M2 |
|
15 m2 |
Specification |
Type |
|
2-wire |
|
3-wire |
|
4-wire |
Alarm Contact |
|
N/A |
|
N/A |
|
0.8A @ 30VDC |
|
|
|
|
|
|
0.4A @ 125VAC |
Thermal Setting |
|
70°C or other selections |
|
|
|
|
Alarm Temperature |
|
Comply to EN54, CNS |
|
|
|
|
Voltage Range |
|
12 ~ 30VDC |
|
|
|
|
|
|
Alarm Current |
|
25 mA |
|
|
|
|
|
|
Ambient Temperature |
|
-10°C ~ +55°C |
|
|
|
|
Material |
|
Comply to EN54, CNS |
|
|
|
|
Dimensions |
|
102 mm (Dia) x 47 mm (H) |
|
|
Weight |
|
About 100g |
|
|
|
|
|
|
Color |
|
White |
|
|
|
|
|
|
|
|
|
|
|
|
|
Photoelectric Smoke Detector S-314 |
|
Effective Alert Area |
|
|
|
|
construction/Height |
|
Under 4M |
|
4M ~ 8M |
Area Covered |
|
150 M2 |
|
75 M2 |
Specification |
Type |
|
2-wire |
|
3-wire |
|
4-wire |
Alarm Contact |
|
N/A |
|
N/A |
|
0.8A @ 30VDC |
|
|
|
|
|
|
0.4A @ 125VAC |
Operating Sensitivity |
|
Comply to UL268, EN54, CNS |
|
|
Operating Current |
|
DC 24V under 30 m |
|
|
|
|
Monitoring Current |
|
Under 75 mA |
|
|
|
|
Ambient Temperature |
|
-10°C ~ +55°C |
|
|
|
|
Material |
|
Fire-proof plastic |
|
|
|
|
Dimensions |
|
102 mm (Dia) x 50 mm (H) |
|
|
Weight |
|
About 170g |
|
|
|
|
|
|
Color |
|
White |
|
|
|
|
|
|
Manual Call Point |
Application |
|
S-334/S-335(with Base) |
|
Adopted Voltage |
|
18 ~ 28VDC(24VDC) |
|
Adopted Current |
|
100mA |
|
|
|
Function |
|
Push Button Emergency, |
|
|
|
Phone Jack, Reset Switch, |
|
|
|
confirmation LED lamp |
|
Coloe |
|
Red |
|
|
|
Size |
|
138mm x 48mm/138mm x 70mm |
Weight |
|
150g/270g |
|
|
Joint Volume |
|
30VDC 1A |
|
|
|
Fire Alarm Bell 6" |
|
|
|
|
|
Voltage |
|
24VDC |
|
|
|
Current |
|
25mA |
|
|
|
Sound Output |
|
93dBA@1M |
|
|
Movement |
|
Motor, Pinion and Striker |
|
Movement |
|
DC motor, acetral gear wheel |
|
Feature |
|
steel striker |
|
|
Gong |
|
Steel, secured with screw |
|
Base Plate |
|
Molded black polycarbonate |
|
Dimensions |
|
6" (152mm) |
|
|
Weight |
|
850g |
|
|
|
Spray Test Smoke
[ Back ]
|
|
|
|
|
|